Fluke T6-600 Electrical Tester with FieldSense, 600V
Fluke T6-600 Electrical Tester with FieldSense, 600V
Orders over $100 ship free
Now you can measure voltage without test leads. Be safer, faster, more efficient. And be everywhere, testing where it used to be impossible.
Measure voltage … without test leads
FieldSense technology lets you slide the open fork over a conductor and see the voltage level.1
- Be safer: Measure voltage to 600 V ac through the open fork, without test leads.
- Be faster: No need to open covers or remove wire nuts.
- Be everywhere: 17.8 mm open fork is widest in the industry; measure up to 200 A on 4/0 wires (120 mm2).
Measure voltage up to 600 V ac through the open fork, without test lead contact to live voltage. Without opening covers or removing wire nuts. On wires up to AWG 4/0 (120 mm2), carrying as much as 200 A. It will change your job. Safer. Faster. Easier.
Product Highlights
- FieldSense technology for ac voltage, current and frequency measurement without making electrical contact to live voltage
- 1 to 600 V ac
- 0.1 to 200 A ac
- True-rms voltage and current
- Resistance 1 Ω to 2000 Ω
- Works with wires up to AWG 4/0 (120 mm2) with a 17.8 mm jaw opening
- HOLD button temporarily freezes the reading for easy viewing
- Easy to read display with backlight
- Accepts optional Fluke TPAK Magnetic Meter Hanger for convenient operation
- Standard two-year warranty; extendable to 4 years through product registration within 45 days of purchase*
Voltage measurement requires capacitive path to ground, provided through user in most applications. Ground connection via test lead may be required in some situations.
* Register product online within 45 days of purchase to extend warranty to four years. See http://a.fluke.com/registration for details. Two-year additional warranty offer may be discontinued without notice
Measurement Specifications | ||||
Function | Requires test leads |
Range | Resolution | Accuracy[1] |
FieldSense ac voltage true-rms |
No | 600 V | 1 V | ±(3% 3 counts) 45 Hz – 66 Hz[2][3] |
FieldSense ac current true-rms |
No | 200.0 A | 0.1 A | ±(3% 3 counts) 45 Hz – 66 Hz |
FieldSense frequency (Hz) |
No | 1 Hz | ±(1% 2 counts)[3] | |
Volts ac true-rms | Yes | 600 V | 1 V | ±(1.5% 2 counts) 45 Hz – 66 Hz |
Volts dc | Yes | 600 V | 1 V | ±(1% 2 counts) |
Resistance | Yes | 2000 Ω | 1 Ω | ±(1% 2 counts) |
Safety | 600 V CAT III | |||
Accuracy[1]: ± ( [ % of reading] [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding. Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground. Accuracy[3]: FieldSense is specified from 16 V to 100 % of range. |
General Specifications | ||
Calibration | 1-year calibration cycle | |
Dimensions | 61.1 x 259.3 x 43.8 mm | |
Jaw opening | 17.8 mm | |
Weight | 0.35 kg (0.78 lb) | |
Temperature | Operating | -10 °C to 50 °C (14 °F to 122 °F) |
Storage | -30 °C to 60 °C (-22 °F to 140 °F) | |
Altitude | Operating | 2,000 m (6,562 feet) |
Storage | 10,000 m (32,808 feet) | |
Relative Humidity | 0% to 90%, 5 °C to 30 °C (41 °F to 86 °F) | |
0% to 75%, 30°C to 40 °C (86 °F to 104 °F) | ||
0% to 45%, 40°C to 50 °C (104 °F to 122 °F) | ||
Battery Type and Life | 2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense | |
Temperature coefficient | 0.1 x (specified accuracy) / °C for <18°C or >28 °C | |
(< 64.4 °F or > 82.4 °F) | ||
Safety | IEC/EN 61010-1: Pollution Degree 2 | |
Electromagnetic Environment | IEC/EN 61326-1: Portable |
Includes:
- Attached test leads with removable 4 mm probe caps, user documentation