Fluke T6-600 Electrical Tester with FieldSense, 600V

T6-600

Fluke T6-600 Electrical Tester with FieldSense, 600V

Orders over $100 ship free

Now you can measure voltage without test leads. Be safer, faster, more efficient. And be everywhere, testing where it used to be impossible.

Measure voltage … without test leads

FieldSense technology lets you slide the open fork over a conductor and see the voltage level.1

  • Be safer: Measure voltage to 600 V ac through the open fork, without test leads.
  • Be faster: No need to open covers or remove wire nuts.
  • Be everywhere: 17.8 mm open fork is widest in the industry; measure up to 200 A on 4/0 wires (120 mm2).

Measure voltage up to 600 V ac through the open fork, without test lead contact to live voltage.  Without opening covers or removing wire nuts. On wires up to AWG 4/0 (120 mm2), carrying as much as 200 A. It will change your job. Safer. Faster. Easier.

Product Highlights

  • FieldSense technology for ac voltage, current and frequency measurement without making electrical contact to live voltage
  • 1 to 600 V ac
  • 0.1 to 200 A ac
  • True-rms voltage and current
  • Resistance 1 Ω to 2000 Ω
  • Works with wires up to AWG 4/0 (120 mm2) with a 17.8 mm jaw opening
  • HOLD button temporarily freezes the reading for easy viewing
  • Easy to read display with backlight
  • Accepts optional Fluke TPAK Magnetic Meter Hanger for convenient operation
  • Standard two-year warranty; extendable to 4 years through product registration within 45 days of purchase*

 Voltage measurement requires capacitive path to ground, provided through user in most applications. Ground connection via test lead may be required in some situations.
* Register product online within 45 days of purchase to extend warranty to four years. See http://a.fluke.com/registration for details. Two-year additional warranty offer may be discontinued without notice

Measurement Specifications
Function Requires
test leads
Range Resolution Accuracy[1]
FieldSense
ac voltage true-rms
No 600 V 1 V ±(3% 3 counts) 45 Hz – 66 Hz[2][3]
FieldSense
ac current true-rms
No 200.0 A 0.1 A ±(3% 3 counts) 45 Hz – 66 Hz
FieldSense
frequency (Hz)
No 1 Hz ±(1% 2 counts)[3]
Volts ac true-rms Yes 600 V 1 V ±(1.5% 2 counts) 45 Hz – 66 Hz
Volts dc Yes 600 V 1 V ±(1% 2 counts)
Resistance Yes 2000 Ω 1 Ω ±(1% 2 counts)
Safety 600 V CAT III
Accuracy[1]: ± ( [ % of reading] [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding. 
Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground.
Accuracy[3]: FieldSense is specified from 16 V to 100 % of range.

 

General Specifications
Calibration 1-year calibration cycle
Dimensions 61.1 x 259.3 x 43.8 mm
Jaw opening 17.8 mm
Weight 0.35 kg (0.78 lb)
Temperature Operating -10 °C to 50 °C (14 °F to 122 °F)
Storage -30 °C to 60 °C (-22 °F to 140 °F)
Altitude Operating 2,000 m (6,562 feet)
Storage 10,000 m (32,808 feet)
Relative Humidity 0% to 90%, 5 °C to 30 °C (41 °F to 86 °F)
0% to 75%, 30°C to 40 °C (86 °F to 104 °F)
0% to 45%, 40°C to 50 °C (104 °F to 122 °F)
Battery Type and Life 2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense
Temperature coefficient 0.1 x (specified accuracy) / °C for <18°C or >28 °C
(< 64.4 °F or > 82.4 °F)
Safety IEC/EN 61010-1: Pollution Degree 2
Electromagnetic Environment IEC/EN 61326-1: Portable

Includes:

  • Attached test leads with removable 4 mm probe caps, user documentation